Single Core 1.9/3.3(3.6)kV Aluminum MV Cable

Single Core 1.9/3.3(3.6)kV Aluminum MV Cable
Details:
Compliance
• Conductor resistance AS/NZS 1125
• Insulation resistance AS/NZS 1429.1
• Voltage test AS/NZS 1429.1
Standard and References
• AS/NZS 1429.1
• AS/NZS 1125
• AS/NZS 3808
Send Inquiry
Download
Description
Technical Parameters
Certification
AL MV Cable

 

Single Core 1.9/3.3(3.6)kV Aluminum MV Cable

1.9/3.3(3.6)kV single core aluminum medium voltage (MV) cable is built with a stranded compacted circular aluminum conductor that complies with AS/NZS 1125 standards, providing a balance of conductivity and weight efficiency. Aluminum, being lighter than copper, makes this cable a cost-effective and less dense alternative for medium-voltage power distribution systems without compromising on performance.

 

characteristics

 

 

Single core aluminum 1.9/3.3(3.6)kV MV cable is widely used in medium-voltage power distribution systems for a variety of industrial, commercial, and infrastructure applications. Its robust design, featuring a stranded compacted circular aluminum conductor and XLPE insulation, makes it an ideal choice for situations where efficient and reliable power transmission is required. This cable is commonly used in electrical substations, utilities, renewable energy installations such as wind and solar farms, and industrial plants where medium-voltage electricity needs to be delivered safely over extended distances.

MV cable application

 

Feature

 

Single Core AL MV Cable

 

* Conductor: Stranded Compacted Circular aluminium conductor as per AS/NZS 1125

* Conductor Screen: Extruded Semi-conductive compound

* Insulation: XLPE * Insulation Screen: Extruded Semi-conductive compound

* Longitudinal Water blocking : Water blocking tape above and below copper screen (Optional)

* Metallic Insulation Screen: Copper Wire Screen + helically applied copper tape (E/F current capacity – Based on requirement)

* Metallic Sheath: Lead Alloy (optional)

* Outer Sheath: Extruded Polyvinyl Chloride, Colour: Black (Alternative Sheath: PVC+HDPE Composite Sheath or LSZH Outer sheath and parameters will change accordingly)

 

Certification

 

 

1.9/3.3(3.6)kV aluminum medium voltage cable complies with AS/NZS 1429.1 standard and has passed SAA certification (SAA numbers: SAA242046 and SAA250307), which can verify on the official website. SAA certification is mandatory for suppliers planning to enter the Oceania market. Certified cables can be legally sold and installed in Australia without regulatory risks or concerns. This helps reduce delays and costs associated with additional inspections or approvals.

SAA medium voltage cable

 

Package

 

THHN wire package

product-15-15

 

Production Line

 

thhn cable factory

 

Greater Wire & Cable Manufacturer is an integration of smart and digital factories designed to increase production speed and more importantly ensure the highest quality standards, with automated production equipment accuracy up to 0.002mm. Every cable produced undergoes a comprehensive 100% inspection throughout the production and inspection process, creating a new era of precision and efficiency. The advanced setup eliminates the inherent errors and defects associated with manual assembly, building on the promise of delivering a product with unparalleled reliability.

 

Case

 

Company cases

product-15-15

 

Partner

 

greater wire Partner

product-15-15

 

FAQ

 

Q: What is mv 105 15kv cable used for?

A:mv 105 15kv cable are mainly used for high-voltage power transmission and distribution. This type of wire is suitable for scenarios that require high voltage transmission, such as transmission lines, substations, industrial plants, and residential areas

Q: What does MV 15 kV cable mean?

A:  15 kV cable indicates that the rated line voltage of the cable is 15 kV. This cable is suitable for transmitting electricity and can operate stably within a voltage range of 15 kV

Q: Is 15kV medium-voltage cable?

A: Yes, 15kV is a medium voltage cable. Medium voltage cables typically refer to those used for voltages between 1000V and 30kV, with 15kV specifically falling within this range, and therefore can be considered as medium voltage cables

 

 

Hot Tags: single core 1.9/3.3(3.6)kv aluminum mv cable, China single core 1.9/3.3(3.6)kv aluminum mv cable manufacturers, suppliers, factory

AL MV Cable

Single Core AL MV Cable

No. of
Cores

 

Core Cross
sectional
Area
Nominal Diameter
Under
metallic
screen
Under
metallic
screen
Overall
No.
mm2
mm
mm
mm
1 16 11.8 13.7 18.0
1 25 13.1 15.0 19.0
1 35 14.1 16.0 20.0
1 50 15.2 17.1 21.0
1 70 16.8 18.7 23.0
1 95 18.4 20.3 24.0
1 120 20 21.9 26.0
1 150 21.3 23.2 27.0
1 185 23 24.9 29.0
1 240 25.3 27.2 31.0
1 300 27.5 29.4 34.0
1 400 30.2 32.1 37.0
1 500 34 35.9 41.0
1 630 37.6 39.5 44.0
1 800 41.9 43.8 49.0
1 1000 46.8 48.7 54.0
• Above mentioned parameters are based on 3k A/sec earth fault current capacity of copper screen
 
ELECTRICAL CHARACTERISTICS:
No.of Cores
Core Cross sectional Area
Max. DC Resistance at 20˚C
Max. AC Resistance at 90˚C
Approx. Capacitance
Approx. Inductance
Approx.

 Reactance

Continuous Current Rating
In ground at  20℃
In Duct at
20℃
In air at 30℃

 Flat

Trefoil
Flat
Trefoil
Flat
Trefoil
No.
mm2
Ω/km
Ω/km
µF/km
mH/km
Ω/km
Amps
1 16 1.91 2.449 0.26 0.467 0.147 88 84 81 80 99 97
1 25 1.2 1.539 0.3 0.431 0.135 112 108 103 102 130 127
1 35 0.868 1.113 0.34 0.411 0.129 134 129 123 122 157 154
1 50 0.641 0.822 0.38 0.392 0.123 157 152 146 142 189 184
1 70 0.443 0.568 0.43 0.362 0.114 192 186 178 176 236 230
1 95 0.32 0.411 0.49 0.345 0.108 229 221 213 210 287 280
1 120 0.253 0.325 0.55 0.328 0.103 260 252 242 240 332 324
1 150 0.206 0.265 0.59 0.319 0.100 288 281 271 267 376 368
1 185 0.164 0.211 0.65 0.309 0.097 324 317 307 303 432 424
1 240 0.125 0.162 0.73 0.298 0.094 373 367 356 351 511 502
1 300 0.1 0.130 0.81 0.289 0.091 419 414 402 397 586 577
1 400 0.0778 0.102 0.9 0.280 0.088 466 470 457 451 676 673
1 500 0.0605 0.081 0.93 0.274 0.086 525 530 510 505 760 750
1 630 0.0469 0.064 0.95 0.269 0.084 580 585 560 555 860 850
1 800 0.0367 0.052 0.99 0.264 0.083 650 655 620 615 960 950
1 1000 0.0291 0.043 1.04 0.259 0.081 715 705 670 665 1060 1050
*: Current Ratings are based on IEC 60502-2 & IEC 60287, Max. Conductor Temperature at 90℃, Ambient temperature at 30℃ in Air / at 20℃ in Ground, Thermal resistivity of Soil 1.5 k.m/W & for earthenware ducts 1.2k.m/W and Depth of Laying 0.8m.
Current rating de-rating factors for other than 30℃ ambient air temperature.
20 25 35 40 45 50 55 60
1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

 

Current rating de-rating factors for other than 20℃ ground temperature.
10 15 25 30 35 40 45 50
1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76

 

No.of Cores
Core Cross sectional Area
Max. pulling tension on conductor
Charging Current per phase
Zero sequence impedance
Electric Stress at Conductor Screen
Short circuit rating of Phase conductor
No. mm² kN Amps/Km Ohms/Km kV/mm kA, I sec
1 16 0.8 0.16 3.61 1.3 1.5
1 25 1.25 0.18 2.70 1.2 2.4
1 35 1.75 0.2 2.27 1.2 3.3
1 50 2.5 0.23 1.98 1.1 4.7
1 70 3.5 0.26 1.73 1.1 6.6
1 95 4.75 0.29 1.57 1.1 9.0
1 120 6 0.33 1.48 1.1 11.3
1 150 7.5 0.35 1.42 1.1 14.2
1 185 9.25 0.39 1.37 1.1 17.4
1 240 12 0.44 1.32 1.0 22.6
1 300 15 0.48 1.29 1.0 28.3
1 400 20 0.54 1.26 1.0 37.6
1 500 25 0.56 1.24 0.9 47.2
1 630 31.5 0.57 1.22 0.9 59.6
1 800 40 0.59 1.21 0.8 75.6
1 1000 50 0.62 1.20 0.7 94.5

 

MV Cable