Single Core Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable

Single Core Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable
Details:
Compliance
• Conductor resistance AS/NZS 1125
• Insulation resistance AS/NZS 1429.1
• Voltage test AS/NZS 1429.1
Standard and References
• AS/NZS 1429.1
• AS/NZS 1125
• AS/NZS 3808
Send Inquiry
Download
Description
Technical Parameters
Certification
Anti-Termite AL MV Cable

 

Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable

Single core anti-termite 1.9/3.3(3.6)kV aluminum unarmored MV cable's composite sheath is specifically designed for added protection. The inner layer is made of extruded polyvinyl chloride (PVC) in orange, while the outer layer is composed of high-density polyethylene (HDPE), providing robust protection against environmental hazards. The anti-termite layer is made from Polyamide (Nylon-12), effectively shielding the cable from damage caused by termites and other pests, which is crucial in areas prone to such risks. This termite-resistant feature ensures the cable's longevity, particularly in tropical and subtropical regions where termite activity is common. MV cable is capable of operating effectively in temperatures ranging from -25°C to +90°C and can even operate up to 105°C in emergency situations.

Min. installation temperature: 0°C

Operating temperature: -25°C to +90°C

Emergency operating temperature: 105°C

(max. operation of 36hrs, at 3 periods for 12 consecutive months use)

Max. Short Circuit Temperature: 250°C

 

characteristics

 

 

Anti-Termite Aluminum 1.9/3.3(3.6)kV MV Cable is designed for medium-voltage power distribution in environments where protection against termites and other environmental hazards is crucial. This cable is ideal for a range of applications that require reliable power transmission, particularly in areas where environmental conditions can pose challenges to standard cables.

MV cable application

 

Feature

 

Anti-Termite MV Cable

 

• Nominal Voltage: 1.9/3.3 (3.6) kV

• Conductor: Stranded Compacted Circular aluminium conductor as per AS/NZS 1125

• Conductor Screen: Extruded Semi-conductive compound

• Insulation: XLPE

• Insulation Screen: Extruded Semi-conductive compound

• Longitudinal Water blocking : Water blocking tape above and below copper screen

• Metallic Insulation Screen: Copper Wire Screen + helically applied copper tape

Composite sheath

• Inner layer : Extruded Polyvinyl Chloride, Colour: Orange

• Termite Protection: Polyamide (Nylon -12)

• Outer layer: HDPE (Black)

 

Certification

 

 

Anti-Termite aluminum 1.9/3.3(3.6)kV medium voltage cable complies with AS/NZS 1429.1 standard and has passed SAA certification. Certification Numbers: SAA242046 and SAA250307.During the certification process, cables undergo rigorous testing for dielectric strength, insulation integrity, flame retardancy, and mechanical durability. These tests ensure that the cables will operate reliably under all conditions after installation, reducing the risk of electrical failures, fires, or power outages.

SAA medium voltage cable

 

Package

 

THHN wire package

product-15-15

 

Production Line

 

thhn cable factory

 

Greater Wire has strong production capacity and is capable of mass producing low-voltage, medium-voltage and high-voltage cables covering a variety of voltage levels. The factory has a complete production process from raw material processing, conductor manufacturing, insulation processing, cabling, sheath molding to finished product testing to ensure efficient production and quality control of cables. According to customer orders, the factory can also flexibly adjust the production line to meet large-scale or customized production needs.

 

Case

 

Company cases

product-15-15

 

Partner

 

greater wire Partner

product-15-15

 

FAQ

 

Q: Are you a manufacturer or trading company?

A:We are a professional manufacturer, offering full control over your order from start to finish. From initial design to final delivery, we ensure every step meets the highest standards.

Q: How can I get a sample ?

A:  Yes, we can provide you with free samples for testing, you only need to pay for the shipping fee.

Q: Is logo printing an option for the cables?

A: Yes, customization with your logo is available for wires and cables.

 

 

Hot Tags: Single Core Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable, China Single Core Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable manufacturers, suppliers, factory, SAA Australia Flat 2C E Electrical TPS Cable, xhhw rw 90 rhw wire, 0 6 1KV Single Core Flexible Cable, spt 1 cable, SAA Orange Circular Cable, Kabel H05RR F

Anti-Termite AL MV Cable

Anti-Termite MV Cable

No. of
Cores

 

Core Cross
sectional
Area
Nominal Diameter
Under
metallic
screen
Under
metallic
screen
Overall
No.
mm2
mm
mm
mm
1 16 11.8 13.7 18.0
1 25 13.1 15.0 21.0
1 35 14.1 16.0 22.0
1 50 15.2 17.1 23.0
1 70 16.8 18.7 25.0
1 95 18.4 20.3 26.0
1 120 20 21.9 28.0
1 150 21.3 23.2 29.0
1 185 23 24.9 31.0
1 240 25.3 27.2 33.0
1 300 27.5 29.4 36.0
1 400 30.2 32.1 39.0
1 500 34 35.9 43.0
1 630 37.6 39.5 47.0
1 800 41.9 43.8 51.0
1 1000 46.8 48.7 57.0
• Above mentioned parameters are based on 3k A/sec earth fault current capacity of copper screen
 
ELECTRICAL CHARACTERISTICS:
No.of Cores
Core Cross sectional Area
Max. DC Resistance at 20˚C
Max. AC Resistance at 90˚C
Approx. Capacitance
Approx. Inductance
Approx.

 Reactance

Continuous Current Rating
In ground at  20℃
In Duct at
20℃
In air at 30℃

 Flat

Trefoil
Flat
Trefoil
Flat
Trefoil
No.
mm2
Ω/km
Ω/km
µF/km
mH/km
Ω/km
Amps
1 16 1.91 2.449 0.26 0.475 0.149 88 84 81 80 99 97
1 25 1.2 1.539 0.3 0.454 0.143 112 108 103 102 130 127
1 35 0.868 1.113 0.34 0.432 0.136 134 129 123 122 157 154
1 50 0.641 0.822 0.38 0.412 0.129 157 152 146 142 189 184
1 70 0.443 0.568 0.43 0.380 0.119 192 186 178 176 236 230
1 95 0.32 0.411 0.49 0.362 0.114 229 221 213 210 287 280
1 120 0.253 0.325 0.55 0.345 0.108 260 252 242 240 332 324
1 150 0.206 0.265 0.59 0.335 0.105 288 281 271 267 376 368
1 185 0.164 0.211 0.65 0.323 0.102 324 317 307 303 432 424
1 240 0.125 0.161 0.73 0.311 0.098 373 367 356 351 511 502
1 300 0.1 0.130 0.81 0.299 0.094 419 414 402 397 586 577
1 400 0.0778 0.102 0.9 0.291 0.091 466 470 457 451 676 673
1 500 0.0605 0.080 0.93 0.284 0.089 525 530 510 505 760 750
1 630 0.0469 0.064 0.95 0.278 0.087 580 585 560 555 860 850
1 800 0.0367 0.052 0.99 0.273 0.086 650 655 620 615 960 950
1 1000 0.0291 0.043 1.04 0.268 0.084 715 705 670 665 1060 1050
*: Current Ratings are based on IEC 60502-2 & IEC 60287, Max. Conductor Temperature at 90℃, Ambient temperature at 30℃ in Air / at 20℃ in Ground, Thermal resistivity of Soil 1.5 k.m/W & for earthenware ducts 1.2k.m/W and Depth of Laying 0.8m.
Current rating de-rating factors for other than 30℃ ambient air temperature.
20 25 35 40 45 50 55 60
1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

 

Current rating de-rating factors for other than 20℃ ground temperature.
10 15 25 30 35 40 45 50
1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76

 

No.of Cores
Core Cross sectional Area
Max. pulling tension on conductor
Charging Current per phase
Zero sequence impedance
Electric Stress at Conductor Screen
Short circuit rating of Phase conductor
No. mm² kN Amps/Km Ohms/Km kV/mm kA, I sec
1 16 0.8 0.16 3.61 1.3 1.5
1 25 1.25 0.18 2.70 1.2 2.4
1 35 1.75 0.2 2.27 1.2 3.3
1 50 2.5 0.23 1.98 1.1 4.7
1 70 3.5 0.26 1.73 1.1 6.6
1 95 4.75 0.29 1.57 1.1 9.0
1 120 6 0.33 1.48 1.1 11.3
1 150 7.5 0.35 1.42 1.1 14.2
1 185 9.25 0.39 1.37 1.1 17.4
1 240 12 0.44 1.32 1.0 22.6
1 300 15 0.48 1.29 1.0 28.3
1 400 20 0.54 1.26 1.0 37.6
1 500 25 0.56 1.24 0.9 47.2
1 630 31.5 0.57 1.22 0.9 59.6
1 800 40 0.59 1.21 0.8 75.6
1 1000 50 0.62 1.20 0.7 94.5

 

MV Cable

MV cable 02

Send Inquiry