Single core anti-termite 1.9/3.3(3.6)kV aluminum unarmored MV cable's composite sheath is specifically designed for added protection. The inner layer is made of extruded polyvinyl chloride (PVC) in orange, while the outer layer is composed of high-density polyethylene (HDPE), providing robust protection against environmental hazards. The anti-termite layer is made from Polyamide (Nylon-12), effectively shielding the cable from damage caused by termites and other pests, which is crucial in areas prone to such risks. This termite-resistant feature ensures the cable's longevity, particularly in tropical and subtropical regions where termite activity is common. MV cable is capable of operating effectively in temperatures ranging from -25°C to +90°C and can even operate up to 105°C in emergency situations.
Min. installation temperature: 0°C
Operating temperature: -25°C to +90°C
Emergency operating temperature: 105°C
(max. operation of 36hrs, at 3 periods for 12 consecutive months use)
Max. Short Circuit Temperature: 250°C
characteristics
Anti-Termite Aluminum 1.9/3.3(3.6)kV MV Cable is designed for medium-voltage power distribution in environments where protection against termites and other environmental hazards is crucial. This cable is ideal for a range of applications that require reliable power transmission, particularly in areas where environmental conditions can pose challenges to standard cables.
Feature
• Nominal Voltage: 1.9/3.3 (3.6) kV
• Conductor: Stranded Compacted Circular aluminium conductor as per AS/NZS 1125
• Conductor Screen: Extruded Semi-conductive compound
• Insulation: XLPE
• Insulation Screen: Extruded Semi-conductive compound
• Longitudinal Water blocking : Water blocking tape above and below copper screen
• Metallic Insulation Screen: Copper Wire Screen + helically applied copper tape
Composite sheath
• Inner layer : Extruded Polyvinyl Chloride, Colour: Orange
• Termite Protection: Polyamide (Nylon -12)
• Outer layer: HDPE (Black)
Certification
Anti-Termite aluminum 1.9/3.3(3.6)kV medium voltage cable complies with AS/NZS 1429.1 standard and has passed SAA certification. Certification Numbers: SAA242046 and SAA250307.During the certification process, cables undergo rigorous testing for dielectric strength, insulation integrity, flame retardancy, and mechanical durability. These tests ensure that the cables will operate reliably under all conditions after installation, reducing the risk of electrical failures, fires, or power outages.
Package
Production Line
Greater Wire has strong production capacity and is capable of mass producing low-voltage, medium-voltage and high-voltage cables covering a variety of voltage levels. The factory has a complete production process from raw material processing, conductor manufacturing, insulation processing, cabling, sheath molding to finished product testing to ensure efficient production and quality control of cables. According to customer orders, the factory can also flexibly adjust the production line to meet large-scale or customized production needs.
Case
Partner
FAQ
Q: Are you a manufacturer or trading company?
Q: How can I get a sample ?
Q: Is logo printing an option for the cables?
Hot Tags: Single Core Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable, China Single Core Anti-Termite 1.9/3.3(3.6)kV Aluminum MV Cable manufacturers, suppliers, factory, SAA Australia Flat 2C E Electrical TPS Cable, xhhw rw 90 rhw wire, 0 6 1KV Single Core Flexible Cable, spt 1 cable, SAA Orange Circular Cable, Kabel H05RR F


|
No. of
Cores
|
Core Cross
sectional
Area
|
Nominal Diameter
|
||
|
Under
metallic
screen
|
Under
metallic
screen
|
Overall
|
||
|
No.
|
mm2
|
mm
|
mm
|
mm
|
| 1 | 16 | 11.8 | 13.7 | 18.0 |
| 1 | 25 | 13.1 | 15.0 | 21.0 |
| 1 | 35 | 14.1 | 16.0 | 22.0 |
| 1 | 50 | 15.2 | 17.1 | 23.0 |
| 1 | 70 | 16.8 | 18.7 | 25.0 |
| 1 | 95 | 18.4 | 20.3 | 26.0 |
| 1 | 120 | 20 | 21.9 | 28.0 |
| 1 | 150 | 21.3 | 23.2 | 29.0 |
| 1 | 185 | 23 | 24.9 | 31.0 |
| 1 | 240 | 25.3 | 27.2 | 33.0 |
| 1 | 300 | 27.5 | 29.4 | 36.0 |
| 1 | 400 | 30.2 | 32.1 | 39.0 |
| 1 | 500 | 34 | 35.9 | 43.0 |
| 1 | 630 | 37.6 | 39.5 | 47.0 |
| 1 | 800 | 41.9 | 43.8 | 51.0 |
| 1 | 1000 | 46.8 | 48.7 | 57.0 |
|
No.of Cores
|
Core Cross sectional Area
|
Max. DC Resistance at 20˚C
|
Max. AC Resistance at 90˚C
|
Approx. Capacitance
|
Approx. Inductance
|
Approx.
Reactance |
Continuous Current Rating
|
|||||
|
In ground at 20℃
|
In Duct at
20℃
|
In air at 30℃
|
||||||||||
|
Flat |
Trefoil
|
Flat
|
Trefoil
|
Flat
|
Trefoil
|
|||||||
|
No.
|
mm2
|
Ω/km
|
Ω/km
|
µF/km
|
mH/km
|
Ω/km
|
Amps
|
|||||
| 1 | 16 | 1.91 | 2.449 | 0.26 | 0.475 | 0.149 | 88 | 84 | 81 | 80 | 99 | 97 |
| 1 | 25 | 1.2 | 1.539 | 0.3 | 0.454 | 0.143 | 112 | 108 | 103 | 102 | 130 | 127 |
| 1 | 35 | 0.868 | 1.113 | 0.34 | 0.432 | 0.136 | 134 | 129 | 123 | 122 | 157 | 154 |
| 1 | 50 | 0.641 | 0.822 | 0.38 | 0.412 | 0.129 | 157 | 152 | 146 | 142 | 189 | 184 |
| 1 | 70 | 0.443 | 0.568 | 0.43 | 0.380 | 0.119 | 192 | 186 | 178 | 176 | 236 | 230 |
| 1 | 95 | 0.32 | 0.411 | 0.49 | 0.362 | 0.114 | 229 | 221 | 213 | 210 | 287 | 280 |
| 1 | 120 | 0.253 | 0.325 | 0.55 | 0.345 | 0.108 | 260 | 252 | 242 | 240 | 332 | 324 |
| 1 | 150 | 0.206 | 0.265 | 0.59 | 0.335 | 0.105 | 288 | 281 | 271 | 267 | 376 | 368 |
| 1 | 185 | 0.164 | 0.211 | 0.65 | 0.323 | 0.102 | 324 | 317 | 307 | 303 | 432 | 424 |
| 1 | 240 | 0.125 | 0.161 | 0.73 | 0.311 | 0.098 | 373 | 367 | 356 | 351 | 511 | 502 |
| 1 | 300 | 0.1 | 0.130 | 0.81 | 0.299 | 0.094 | 419 | 414 | 402 | 397 | 586 | 577 |
| 1 | 400 | 0.0778 | 0.102 | 0.9 | 0.291 | 0.091 | 466 | 470 | 457 | 451 | 676 | 673 |
| 1 | 500 | 0.0605 | 0.080 | 0.93 | 0.284 | 0.089 | 525 | 530 | 510 | 505 | 760 | 750 |
| 1 | 630 | 0.0469 | 0.064 | 0.95 | 0.278 | 0.087 | 580 | 585 | 560 | 555 | 860 | 850 |
| 1 | 800 | 0.0367 | 0.052 | 0.99 | 0.273 | 0.086 | 650 | 655 | 620 | 615 | 960 | 950 |
| 1 | 1000 | 0.0291 | 0.043 | 1.04 | 0.268 | 0.084 | 715 | 705 | 670 | 665 | 1060 | 1050 |
| 20 | 25 | 35 | 40 | 45 | 50 | 55 | 60 |
| 1.08 | 1.04 | 0.96 | 0.91 | 0.87 | 0.82 | 0.76 | 0.71 |
| 10 | 15 | 25 | 30 | 35 | 40 | 45 | 50 |
| 1.07 | 1.04 | 0.96 | 0.93 | 0.89 | 0.85 | 0.80 | 0.76 |
|
No.of Cores
|
Core Cross sectional Area
|
Max. pulling tension on conductor
|
Charging Current per phase
|
Zero sequence impedance
|
Electric Stress at Conductor Screen
|
Short circuit rating of Phase conductor
|
| No. | mm² | kN | Amps/Km | Ohms/Km | kV/mm | kA, I sec |
| 1 | 16 | 0.8 | 0.16 | 3.61 | 1.3 | 1.5 |
| 1 | 25 | 1.25 | 0.18 | 2.70 | 1.2 | 2.4 |
| 1 | 35 | 1.75 | 0.2 | 2.27 | 1.2 | 3.3 |
| 1 | 50 | 2.5 | 0.23 | 1.98 | 1.1 | 4.7 |
| 1 | 70 | 3.5 | 0.26 | 1.73 | 1.1 | 6.6 |
| 1 | 95 | 4.75 | 0.29 | 1.57 | 1.1 | 9.0 |
| 1 | 120 | 6 | 0.33 | 1.48 | 1.1 | 11.3 |
| 1 | 150 | 7.5 | 0.35 | 1.42 | 1.1 | 14.2 |
| 1 | 185 | 9.25 | 0.39 | 1.37 | 1.1 | 17.4 |
| 1 | 240 | 12 | 0.44 | 1.32 | 1.0 | 22.6 |
| 1 | 300 | 15 | 0.48 | 1.29 | 1.0 | 28.3 |
| 1 | 400 | 20 | 0.54 | 1.26 | 1.0 | 37.6 |
| 1 | 500 | 25 | 0.56 | 1.24 | 0.9 | 47.2 |
| 1 | 630 | 31.5 | 0.57 | 1.22 | 0.9 | 59.6 |
| 1 | 800 | 40 | 0.59 | 1.21 | 0.8 | 75.6 |
| 1 | 1000 | 50 | 0.62 | 1.20 | 0.7 | 94.5 |