6.35/11Kv 3 Core Copper Medium Voltage Cable

6.35/11Kv 3 Core Copper Medium Voltage Cable
Details:
Compliance
• Conductor resistance AS/NZS 1125
• Insulation resistance AS/NZS 1429.1
• Voltage test AS/NZS 1429.1
Standard and References
• AS/NZS 1429.1
• AS/NZS 1125
• AS/NZS 3808
Send Inquiry
Download
Description
Technical Parameters
Certification

Dongguan Greater Wire & Cable Co., Ltd. is one of the leading manufacturers and suppliers of 6.35/11kv 3 core copper medium voltage cable in China, also supports customized service. Please rest assured to wholesale durable 6.35/11kv 3 core copper medium voltage cable made in China here from our factory. If you have any enquiry about free sample, please feel free to email us.

 

3 Ccore copper MV Cable

 

6.35/11Kv 3 Core Copper Medium Voltage Cable

The insulation material of the 3 core aluminum conductor medium voltage cable has high temperature resistance and can operate stably in high temperature environments. Its design temperature range is usually between -25°C and +90°C, which is suitable for use in extreme temperature conditions. The high temperature resistance ensures that the cable will not experience insulation aging or performance degradation under high temperature loads, improving the safety and reliability of the equipment.

Min. installation temperature: 0°C

Operating temperature: -25°C to +90°C

 

Application

 

 

6.35/11kV 3 core copper medium voltage cable is commonly used in municipal infrastructure projects, particularly urban rail transit systems, light industrial parks, and local distribution networks. Its copper conductors offer excellent conductivity and stable voltage transmission, which are crucial for applications requiring high-reliability power supply over short distances. For example, this cable is commonly used to power subway substations, sewage treatment facilities, and distributed generation systems such as gas-fired power plants or small wind farms. Rated at 11kV, this cable is ideal for medium-voltage power distribution between 6kV rated equipment and regional substations, ensuring safety, efficiency, and installation flexibility.

MV cable application

 

Feature

 

3C copper MV Cable

 

• Conductor: Stranded Compacted Circular Copper conductor as per AS/NZS 1125

• Conductor Screen: Extruded Semi-conductive compound

• Insulation: XLPE

• Insulation Screen: Extruded Semi-conductive compound

• Longitudinal Water blocking: Water blocking tape below copper screen (Optional)

• Metallic Insulation Screen: Copper Wire Screen + helically applied copper tape (E/F current capacity – Based on requirement)

• binder tape/sheath over assembled cores

• Metallic Sheath: Lead Alloy (optional)

• Outer Sheath: Extruded Polyvinyl Chloride, Colour: Black

• Insect attack Protection: Polyamide Nylon (optional)

(Alternative Sheath: PVC+HDPE Composite Sheath or PVC + Nylon + HDPE (composite sheath with anti-termite properties) or LSZH Outer sheath, and parameters will change accordingly)

 

Certification

 

 

3 core aluminum MV wire has passed SAA certification. SAA certification numbers SAA242046 and SAA250307, which customers can verify on the official website. SAA certified MV wire is flame-retardant, fire-resistant, and chemical-resistant, making it safe for use in chemical plants and other industrial environments, and the cable provides power continuity.

SAA medium voltage cable

 

Package

 

sta power cable package

 

Factory

 

SAA cable factory

 

Our cables and wires have passed SAA, UL, TUV, CE, and other standard certifications.Our products have gained tremendous traction in the international market and are frequently exported to regions such as Southeast Asia, Australia, the Middle East, Africa, America, and Europe, Sales cover more than 400 cities at home and abroad.Greater Wire Company has developed a strong team encompassing research and development, technical expertise, sales, production, and quality inspection, which ensures that from wire and cable design to project implementation, we can provide professional and high-quality services to meet the various needs of customers with excellent quality.Our commitment to quality and customer satisfaction has made Greater Wire a trusted partner to the global wire and cable industry.

 

Case

 

Company cases

 

Partner

 

greater wire Partner

 

FAQ

 

Q: How to deal with cable connectors?

A: When handling joints, it is essential to ensure both safety and reliability to maintain proper operation and prevent failures. 
1. Select appropriate joint materials: Choose suitable kits and accessories based on conductor type, voltage rating, and installation environment. For medium-voltage applications, cold-shrink or heat-shrink solutions are commonly used.
2. Confirm power-off status: Make sure the line is completely de-energized, perform voltage tests, and avoid live work. Prepare the necessary stripping tools, insulation tape, conductive adhesive, and joint kits to ensure safe and efficient construction.
3. Strip the layers: Following joint design requirements, use professional tools to carefully remove the outer sheath, shielding, insulation, and semi-conductive layers
4. Connect the conductors. Use appropriate crimping or welding methods to connect the conductors to ensure the current conduction performance of the conductors.
5. Install the joint sleeve. According to the type of joint, put the insulating tube or insulating material layer by layer on the conductor connection to ensure the insulation of the joint.
6. Sealing and waterproofing. Use waterproof sealing tape or special joint seals to seal the joint part to prevent moisture, humidity or other external contaminants from entering the joint.
7. After the connector is installed, perform electrical tests such as insulation resistance test, withstand voltage test and continuity test to ensure that the connector is normal and performs well.
8. Record the installation date, location and connector type of the connector, and place permanent marks to facilitate identification of the connector location during future maintenance.
9. Post-inspection and maintenance, regularly check the status of the connector, especially in extreme temperature or humid environments, to prevent aging, loosening or other damage.

Q:  Are you a manufacturer or trading company?

A:  We are a professional manufacturer, offering full control over your order from start to finish. From initial design to final delivery, we ensure every step meets the highest standards.

Q:  How can I get a sample?

A: Yes, we can provide you with free samples for testing, you only need to pay for the shipping fee.

 

 

 

Hot Tags: 6.35/11kv 3 core copper medium voltage cable, China 6.35/11kv 3 core copper medium voltage cable manufacturers, suppliers, factory, 3 8 7 2Kv Aluminum 3C Medium Voltage Industrial Cable, AS NZS1429 1 Single Core Aluminum 19 33kV MV Unarmored Cable, Medium Voltage Unarmoured Cable 3 Core 3 8 6 6Kv Copper Wire, Mv 105 15kv Cable, Single Core 1 9 3 3 3 6 kV Aluminum MV Cable, Three Core 12 7 24Kv Aluminum MV Cable

3C copper MV Cable

3C copper MV power Cable

No. of
Cores
Core Cross
sectional
Area
Nominal Diameter
Under
metallic
screen
Under
metallic
screen
Overall
No.
mm2
mm
mm
mm
3 16 14.7 16.2 39.0
3 25 15.9 17.4 42.0
3 35 16.9 18.4 44.0
3 50 18 19.5 47.0
3 70 19.7 21.2 51.0
3 95 21.2 22.7 54.0
3 120 22.8 24.3 58.0
3 150 24.2 25.7 61.0
3 185 25.9 27.4 65.0
3 240 28.2 29.7 70.0
3 300 30.2 31.7 75.0
3 400 33 34.5 81.0
3 500 36.4 37.9 89.0
• Above mentioned parameters are based on 3k A/sec earth fault current capacity of copper screen
 
ELECTRICAL CHARACTERISTICS:
No.of Cores
Core Cross sectional Area
Max. DC Resistance at 20˚C
Max. AC Resistance at 90˚C
Approx. Capacitance
Approx. Inductance
Approx.

 Reactance

Continuous Current Rating
Buried direet in ground
In a buried duct
In Air 
No.
mm2
Ω/km
Ω/km
µF/km
mH/km
Ω/km
Amps
3 16 1.15 1.446 0.18 0.637 0.200 101 87 109
3 25 0.727 0.927 0.2 0.605 0.190 129 112 142
3 35 0.524 0.668 0.22 0.583 0.183 153 133 170
3 50 0.387 0.494 0.25 0.565 0.177 181 158 204
3 70 0.268 0.342 0.28 0.533 0.168 221 193 253
3 95 0.193 0.247 0.31 0.518 0.163 262 231 304
3 120 0.153 0.196 0.35 0.501 0.157 298 264 351
3 150 0.124 0.159 0.38 0.491 0.154 334 297 398
3 185 0.0991 0.127 0.41 0.481 0.151 377 336 455
3 240 0.0754 0.097 0.46 0.469 0.147 434 390 531
3 300 0.0601 0.078 0.5 0.459 0.144 489 441 606
3 400 0.047 0.062 0.56 0.450 0.141 553 501 696
3 500 0.0366 0.049 0.63 0.440 0.138 632 574 800
*: Current Ratings are based on IEC 60502-2 & IEC 60287, Max. Conductor Temperature at 90℃, Ambient temperature at 30℃ in Air / at 20℃ in Ground, Thermal resistivity of Soil 1.5 k.m/W & for earthenware ducts 1.2k.m/W and Depth of Laying 0.8m.
Current rating de-rating factors for other than 30℃ ambient air temperature.
20 25 35 40 45 50 55 60
1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

 

Current rating de-rating factors for other than 20℃ ground temperature.
10 15 25 30 35 40 45 50
1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76

 

No.of Cores
Core Cross sectional Area
Max. pulling tension on conductor
Charging Current per phase
Zero sequence impedance
Electric Stress at Conductor Screen
Short circuit rating of Phase conductor
No. mm² kN Amps/Km Ohms/Km kV/mm kA, I sec
3 16 1.12 0.36 2.63 2.8 2.3
3 25 1.75 0.4 2.09 2.7 3.6
3 35 2.45 0.44 1.83 2.6 5.0
3 50 3.5 0.5 1.65 2.5 7.2
3 70 4.9 0.56 1.50 2.4 10.0
3 95 6.65 0.62 1.41 2.3 13.6
3 120 8.4 0.7 1.36 2.3 17.1
3 150 10.5 0.76 1.32 2.3 21.4
3 185 12.95 0.82 1.29 2.2 26.4
3 240 16.8 0.92 1.26 2.2 34.3
3 300 21 1 1.24 2.2 42.8
3 400 28 1.12 1.22 2.1 56.9
3 500 35 1.26 1.21 2.1 71.5

 

MV Cable

MV cable 02