- Type of conductor: Stranded copper
- Conductor Type: single core (2C+E/3C+E/4C+E are available)
- Insulation: X-90 insulation
- Sheath: 5V-90 sheath
- Rated Voltage Uo/U (Um): 0.6/1 kV
- Standard: AS/NZS 5000.1
- Color: Black/Orange
Application
0.6/1kV single core XLPE cable is made of cross-linked polyethylene (XLPE) as insulation material and polyvinyl chloride (PVC) as outer sheath, which complies with AS/NZS5000.1 standard. This cable is suitable for main power supply, power sub-power supply and branch cable of various buildings and industrial equipment, and is widely used in unenclosed, enclosed in conduit, buried or underground pipeline, and is not subject to mechanical damage. 0.6/1kV single core XLPE cable is particularly suitable for use in places with tight space or possible overload, and has excellent electrical performance and heat resistance. Its cross-linked polyethylene insulation layer can effectively prevent electrical breakdown and ensure that the cable maintains stable electrical performance in long-term operation, and is suitable for various low-voltage power transmission and distribution systems.

Feature

0.6/1kV single-core XLPE cable conductor type is single-core (optional 2C+E, 3C+E or 4C+E configuration), suitable for different power system requirements. Its insulation material uses advanced X-90 cross-linked polyethylene (XLPE), which has excellent heat resistance, voltage breakdown resistance and chemical stability, ensuring long-term stable operation of the cable under high temperature and complex environment. The outer sheath uses 5V-90 PVC material, which has good anti-aging, corrosion resistance and mechanical strength, and can provide effective protection in various harsh environments. There are two exterior colors available: black and orange to meet different installation requirements.
Certification
Cables have passed SAA certifications.. The X-90 version carries SAA-240462-EA and SAA240463 approvals, and the V-90 variant is authorized under SAA-241265-EA. All certificates support real-time verification on the SAA site, giving end users full confidence. Our company has corresponding certifications for each region. We have more than 10 years of experience in foreign trade export, exporting to more than 90 countries around the world, and are familiar with the wire and cable specifications and standards of many countries.

Package
Production Line

Dongguan Greater Wire & Cable Co., Ltd. was established in 1995, it is a professional wire and cable manufacturer. Our company has advanced production equipment and production technology, complete testing equipment, and strong product technology strength. After years of hard work and the support of clients from all over the World, our company has developed rapidly and won a high honor and share in overseas markets. The company has passed the ls09001 quality management system certification, National high tech enterprise certification, national specialization, and special new enterprise certification.
Case
Partner
FAQ
Q: Are you a manufacturer or trading company?
Q: What's your Minimum Order Quantity?
Hot Tags: 0.6/1kv single core xlpe cable, China 0.6/1kv single core xlpe cable manufacturers, suppliers, factory, xlpe armoured cable, 300V CSA VW 1 UL1007 Hook Up Wire, spt 1 cable, HO7V-U, ul1015 hook up wire, AC Power Cable
Single Core | ||||||
Conductor | Cable | Min installed bending radius(a)mm | ||||
Nominal C.S.A. |
Number and diameter of wires No/mm | Nominal insulation thickness mm |
Overall diameter mm | Approx. mass kg/100m | ||
Minimum mm | Maximum mm | |||||
25 | 7/2.12 | 0.9 | 10.9 | 11.4 | 32 | 45 |
35 | 7/2.50 | 0.9 | 12.0 | 12.6 | 42 | 50 |
50 | 19/1.80 | 1.0 | 13.5 | 14.1 | 55 | 55 |
70 | 19/2.14 | 1.1 | 15.4 | 16.0 | 74 | 65 |
95 | 19/2.50 | 1.1 | 17.5 | 18.2 | 102 | 75 |
120 | 37/2.01 | 1.2 | 19.3 | 20.0 | 126 | 80 |
150 | 37/2.24 | 1.4 | 21.4 | 22.2 | 154 | 90 |
185 | 37/2.50 | 1.6 | 23.6 | 24.4 | 192 | 100 |
240 | 61/2.25 | 1.7 | 26.6 | 27.4 | 248 | 165 |
300 | 61/2.52 | 1.8 | 29.3 | 30.3 | 309 | 180 |
400 | 61/2.85 | 2.0 | 32.8 | 33.8 | 391 | 200 |
500 | 61/3.20 | 2.2 | 34.6 | 35.5 | 492 | 215 |
630 | 61/3.62 | 2.4 | 39.0 | 40.0 | 628 | 240 |
2 Core and Earth (2C+E) | ||||||
Conductor | Cable | Min installed bending radius(a)mm | ||||
Nominal C.S.A. |
Number and diameter of wires No/mm | Nominal insulation thickness mm |
Overall diameter mm | Approx. mass kg/100m | ||
Minimum mm | Maximum mm | |||||
1.5 | 7/0.52 | 0.7 | 9.6 | 10.4 | 15 | 42 |
2.5 | 7/0.67 | 0.7 | 10.8 | 11.7 | 20 | 47 |
4 | 7/0.85 | 0.7 | 11.6 | 12.5 | 25 | 50 |
6 | 7/1.04 | 0.7 | 12.6 | 13.6 | 30 | 54 |
10 | 7/1.35 | 0.7 | 14.4 | 15.4 | 42 | 62 |
16 | 7/1.70 | 0.7 | 16.8 | 17.7 | 55 | 71 |
3 Core and Earth (3C+E) | ||||||
Conductor | Cable | Min installed bending radius(a)mm | ||||
Nominal C.S.A. |
Number and diameter of wires No/mm | Nominal insulation thickness mm |
Overall diameter mm | Approx. mass kg/100m | ||
Minimum mm | Maximum mm | |||||
25 | 7/2.12 | 0.9 | 21.6 | 22.6 | 104 | 90 |
35 | 7/2.50 | 0.9 | 24.2 | 25.3 | 137 | 150 |
50 | 19/1.80 | 1.0 | 27.4 | 28.7 | 185 | 170 |
70 | 19/2.14 | 1.1 | 32.1 | 33.3 | 256 | 200 |
95 | 19/2.50 | 1.1 | 36.0 | 37.3 | 339 | 220 |
120 | 37/2.01 | 1.2 | 40.1 | 41.4 | 425 | 250 |
150 | 37/2.24 | 1.4 | 44.8 | 46.3 | 528 | 280 |
185 | 37/2.50 | 1.6 | 50.4 | 51.9 | 669 | 310 |
240 | 61/2.25 | 1.7 | 56.9 | 58.5 | 872 | 350 |
300 | 61/2.52 | 1.8 | 63.0 | 64.8 | 1089 | 390 |
4 Core and Earth (4C+E) | ||||||
Conductor | Cable | Min installed bending radius(a)mm | ||||
Nominal C.S.A. |
Number and diameter of wires No/mm | Nominal insulation thickness mm |
Overall diameter mm | Approx. mass kg/100m | ||
Minimum mm | Maximum mm | |||||
16 | 7/1.70 | 0.7 | 19.59 | 21.6 | 87.2 | 85 |
25 | 7/2.12 | 0.9 | 24.0 | 25.1 | 132 | 150 |
35 | 7/2.50 | 0.9 | 26.8 | 28.1 | 175 | 170 |
50 | 19/1.80 | 1.0 | 30.8 | 32.2 | 237 | 190 |
70 | 19/2.14 | 1.1 | 36.1 | 37.3 | 328 | 220 |
95 | 19/2.50 | 1.1 | 40.6 | 42.1 | 439 | 250 |
120 | 37/2.01 | 1.2 | 45.3 | 46.7 | 550 | 280 |
150 | 37/2.24 | 1.4 | 50.7 | 52.3 | 684 | 310 |
185 | 37/2.50 | 1.6 | 57.0 | 58.6 | 862 | 350 |
240 | 61/2.25 | 1.7 | 64.4 | 66.2 | 1127 | 400 |
300 | 61/2.52 | 1.8 | 71.3 | 73.3 | 1407 | 440 |