12.7/24kV Anti-Termite medium voltage cable is durability, chemical-resistant, UV protection. Medium voltage Cable has a metal insulation screen consisting of a copper wire screen and a spiral copper tape. Copper has excellent conductivity and corrosion resistance. The copper wire screen ensures a low impedance path for fault current, providing a reliable grounding system. MV cable uses a metal insulation screen to prevent electrical interference and faults. It acts as a shield, providing an effective grounding path in the event of an insulation fault, thereby improving safety. In addition, the spiral copper tape ensures uniform coverage, further reducing the risk of electrical hazards.
characteristics
Single core 12.7/24kV aluminum anti-termite medium voltage cable can be used for power distribution in large infrastructure, power generation stations, and mechanical equipment in mines such as mining machines and hoists that rely on medium voltage cables for power supply. Due to the humid environment in mines, cables with excellent moisture resistance and mechanical shock resistance are required to ensure safe operation.
Feature
• Conductor: Stranded Compacted Circular aluminium conductor as per AS/NZS 1125
• Conductor Screen: Extruded Semi-conductive compound
• Insulation: XLPE
• Insulation Screen: Extruded strippable Semi-conductive compound
• Longitudinal Water blocking: Water blocking tape above and below copper screen (Optional)
• Metallic Insulation Screen: Copper Wire Screen + helically applied copper tape (E/F current capacity – Based on requirement)
Composite sheath
• Inner layer: Extruded Polyvinyl Chloride, Colour: Orange
• Termite Protection: Polyamide (Nylon -12)
• Outer layer: HDPE (Black)
• Min. installation temperature: 0°C
• Operating temperature: -25°C to +90°C
• Emergency operating temperature: 105°C
(max. operation of 36 hours, at 3 periods for 12 consecutive months use)
• Max. Short Circuit Temperature: 250°C
Certification
12.7/24kV medium voltage cable has obtained SAA certification, with certification numbers: SAA242046 and SAA250307 (available on the certification website). Certified cables are less prone to defects and premature failures, significantly reducing the risk of unexpected costs or liabilities for customers. Project auditors often favor certified products, as they reduce the risk of incidents and claims. For project owners, selecting SAA-certified cables reduces operational risk while also securing their long-term investment. Essentially, SAA certification effectively manages and mitigates risk throughout the cable's entire service life.
Package
Production Line
Greater Wire Manufacturer is very strict in the selection of raw materials. It uses high-purity copper, aluminum, and other conductor materials provided by internationally renowned suppliers, and also uses high-quality XLPE (cross-linked polyethylene), PVC (polyvinyl chloride), and other insulation materials. In order to ensure the stability of the cable in different environments, the factory also selects sheath materials with fire-resistant, moisture-proof, and UV-resistant properties. Through precise material control, the factory ensures that the cable has excellent electrical performance and a long service life.
Case
Partner
FAQ
Q: Are you a manufacturer or trading company?
Q: How can we guarantee quality?
Q: How can I get a sample?
Hot Tags: single core 12.7/24kv aluminum anti-termite medium voltage cable, China single core 12.7/24kv aluminum anti-termite medium voltage cable manufacturers, suppliers, factory, 2 3 4 5 Core Kabel H05VV F, 110 elastomer cables, CUL Standard XLPE Copper RW75 RW9O RWU75 RWU90 Cable, AS NZS5000 1 Aerial Parallel Cable, SAA Approval SDI Cable, 110 Single Core Elastomer Cables


|
No. of
Cores
|
Core Cross
sectional
Area
|
Nominal Diameter
|
||
|
Under
metallic
screen
|
Under
metallic
screen
|
Overall
|
||
|
No.
|
mm2
|
mm
|
mm
|
mm
|
| 1 | 35 | 21.1 | 23.0 | 29.0 |
| 1 | 50 | 22.2 | 24.1 | 30.0 |
| 1 | 70 | 23.8 | 25.7 | 32.0 |
| 1 | 95 | 25.4 | 27.3 | 34.0 |
| 1 | 120 | 27 | 28.9 | 36.0 |
| 1 | 150 | 28.3 | 30.2 | 37.0 |
| 1 | 185 | 30 | 31.9 | 39.0 |
| 1 | 240 | 32.3 | 34.2 | 41.0 |
| 1 | 300 | 34.5 | 36.4 | 43.0 |
| 1 | 400 | 37.2 | 39.1 | 46.0 |
| 1 | 500 | 40.6 | 42.5 | 50.0 |
| 1 | 630 | 43.8 | 45.7 | 53.0 |
| 1 | 800 | 47.7 | 49.6 | 58.0 |
| 1 | 1000 | 52.2 | 54.1 | 63.0 |
|
No.of Cores
|
Core Cross sectional Area
|
Max. DC Resistance at 20˚C
|
Max. AC Resistance at 90˚C
|
Approx. Capacitance
|
Approx. Inductance
|
Approx.
Reactance |
Continuous Current Rating
|
|||||
|
In ground at 20℃
|
In Duct at
20℃
|
In air at 30℃
|
||||||||||
|
Flat |
Trefoil
|
Flat
|
Trefoil
|
Flat
|
Trefoil
|
|||||||
|
No.
|
mm2
|
Ω/km
|
Ω/km
|
µF/km
|
mH/km
|
Ω/km
|
Amps
|
|||||
| 1 | 35 | 0.868 | 1.113 | 0.16 | 0.488 | 0.153 | 134 | 129 | 123 | 122 | 157 | 154 |
| 1 | 50 | 0.641 | 0.822 | 0.17 | 0.466 | 0.146 | 157 | 152 | 146 | 142 | 189 | 184 |
| 1 | 70 | 0.443 | 0.568 | 0.2 | 0.433 | 0.136 | 192 | 186 | 178 | 176 | 236 | 230 |
| 1 | 95 | 0.32 | 0.411 | 0.22 | 0.412 | 0.129 | 229 | 221 | 213 | 210 | 287 | 280 |
| 1 | 120 | 0.253 | 0.325 | 0.24 | 0.394 | 0.124 | 260 | 252 | 242 | 240 | 332 | 324 |
| 1 | 150 | 0.206 | 0.265 | 0.25 | 0.380 | 0.119 | 288 | 281 | 271 | 267 | 376 | 368 |
| 1 | 185 | 0.164 | 0.211 | 0.28 | 0.368 | 0.116 | 324 | 317 | 307 | 303 | 432 | 424 |
| 1 | 240 | 0.125 | 0.161 | 0.31 | 0.351 | 0.110 | 373 | 367 | 356 | 351 | 511 | 502 |
| 1 | 300 | 0.1 | 0.130 | 0.33 | 0.339 | 0.106 | 419 | 414 | 402 | 397 | 586 | 577 |
| 1 | 400 | 0.0778 | 0.102 | 0.37 | 0.327 | 0.103 | 466 | 470 | 457 | 451 | 676 | 673 |
| 1 | 500 | 0.0605 | 0.080 | 0.41 | 0.315 | 0.099 | 525 | 530 | 510 | 505 | 760 | 750 |
| 1 | 630 | 0.0469 | 0.064 | 0.45 | 0.306 | 0.096 | 580 | 585 | 560 | 555 | 860 | 850 |
| 1 | 800 | 0.0367 | 0.051 | 0.5 | 0.296 | 0.093 | 650 | 655 | 620 | 615 | 960 | 950 |
| 1 | 1000 | 0.0291 | 0.043 | 0.56 | 0.288 | 0.091 | 715 | 705 | 670 | 665 | 1060 | 1050 |
| 20 | 25 | 35 | 40 | 45 | 50 | 55 | 60 |
| 1.08 | 1.04 | 0.96 | 0.91 | 0.87 | 0.82 | 0.76 | 0.71 |
| 10 | 15 | 25 | 30 | 35 | 40 | 45 | 50 |
| 1.07 | 1.04 | 0.96 | 0.93 | 0.89 | 0.85 | 0.80 | 0.76 |
|
No.of Cores
|
Core Cross sectional Area
|
Max. pulling tension on conductor
|
Charging Current per phase
|
Zero sequence impedance
|
Electric Stress at Conductor Screen
|
Short circuit rating of Phase conductor
|
| No. | mm² | kN | Amps/Km | Ohms/Km | kV/mm | kA, I sec |
| 1 | 35 | 1.75 | 0.64 | 2.27 | 3.7 | 3.3 |
| 1 | 50 | 2.5 | 0.68 | 1.98 | 3.5 | 4.7 |
| 1 | 70 | 3.5 | 0.8 | 1.73 | 3.4 | 6.6 |
| 1 | 95 | 4.75 | 0.88 | 1.57 | 3.2 | 9.0 |
| 1 | 120 | 6 | 0.96 | 1.48 | 3.1 | 11.3 |
| 1 | 150 | 7.5 | 1 | 1.42 | 3.1 | 14.2 |
| 1 | 185 | 9.25 | 1.12 | 1.37 | 3.0 | 17.4 |
| 1 | 240 | 12 | 1.24 | 1.32 | 2.9 | 22.6 |
| 1 | 300 | 15 | 1.32 | 1.29 | 2.9 | 28.3 |
| 1 | 400 | 20 | 1.48 | 1.26 | 2.8 | 37.6 |
| 1 | 500 | 25 | 1.64 | 1.24 | 2.7 | 47.2 |
| 1 | 630 | 31.5 | 1.8 | 1.22 | 2.7 | 59.6 |
| 1 | 800 | 40 | 1.99 | 1.21 | 2.7 | 75.6 |
| 1 | 1000 | 50 | 2.23 | 1.20 | 2.6 | 94.5 |