35kV Concentric Neutral Cable Aluminum TR-XLPE Medium Voltage Primary UD MV105 Wire 100% I. L. 345 Mils

35kV Concentric Neutral Cable Aluminum TR-XLPE Medium Voltage Primary UD MV105 Wire 100% I. L. 345 Mils
Details:
·Aluminum Stranded Conductor(unfilled/filled)
·XLPE Jacket with 3 Red Stripes
·Insulation Shield
·Conductor Shield
·TR-XLPE Insulation
·Copper Wire Concentric Neutral
·Voltage Rating:35KV
·Size Range:1/0AWG~1500kcmil
·Standard:UL1072
·Single core
·Color:black
Send Inquiry
Download
Description
Technical Parameters
Certification

MV-105 Type Primary UD 35kV 100% cable

PRODUCT REAL SHOT

 

moisture blocked XLPE jacket MV-105 cable cost
buy 35kV 345 mils MV-105 cable
35kV 345 mils TR-XLPE Primary UD cable

MV-105 Type Primary UD 35kV 100% cable

35kV Aluminum TR-XLPE/CN/XLPE MV-105 Primary UD Cable 100% I.L. 345 mils
When both high voltage and high temperature are the norm, MV-105 rated cable provides the thermal capacity that MV-90 cannot match. This 35kV primary UD cable operates continuously at 105°C conductor temperature, delivering higher ampacity in hot environments like power generation stations and heavy industrial plants. The aluminum conductor is insulated with 345 mils of TR-XLPE, shielded with copper tape, and jacketed with rugged XLPE featuring three red stripes for quick visual identification in crowded underground facilities. UL1072 certified with 100% insulation level, this cable offers standard dielectric protection for 35kV systems with the added benefit of superior thermal performance. The XLPE jacket provides excellent resistance to moisture, chemicals, and mechanical stress, ensuring long-term reliability in underground duct and direct burial installations. TR-XLPE insulation provides enhanced resistance to water treeing, extending service life in the wet underground conditions where 35kV distribution cables are typically installed. This is the choice for the most demanding 35kV applications where both electrical and thermal stress are at their peak.
PRODUCT SPECIFICATIONS

 

35kV TR-XLPE CN XLPE cable

Product Description

 

The Medium Voltage Underground Distribution (UD) cables consist of an Aluminum stranded conductor,(filled or unfilled)  covered with tree-retardant cross-linked polyethylene (TR-XLPE), a concentric neutral of helically applied copper wires, and a cross-linked(filled or unfilled) polyethylene (XLPE) jacket with 3 extruded cross-linked red stripes.

Applications

 
  • Suitable for underground primary power applications
  • For wet or dry locations
  • For direct burial or in duct

Features

 
  • High dielectric strength
  • Low moisture absorption
  • Low dielectric loss
  • Excellent resistance to treeing
  • Jacket is sunlight-resistant
  • Designed to operate continuously at a conductor temperature not exceeding

    105°C for normal operations

    140°C for emergency overload

    250°C for short circuit

SPECIFICATIONS

Conductor Count

1 conductor

Conductor

Aluminum 1350 Class B compressed strand (filled or unfilled)

Gauge Sizes

Available in 1/0 AWG through 1500 kcmil

Conductor Strand Shield

Extruded thermoset semi-conducting polymer over the conductor

Insulation

Tree-Retardant Cross-linked Polyethylene (TR-XLPE)

Insulation Shield

Extruded thermoset semi-conducting polymer over the insulation

Neutral

Helically applied, annealed, solid bare copper wires

Jacket

Cross-Linked Polyethylene (XLPE)

  • Moisture blocked jacket is available upon on request

Jacket Marking

00000 FT GREATER WIRE XXAWG (KCMIL) AL(FS) 1/C XXKV XXX% INSUL LEVEL XXXMILS TRXLPE AA X #BB XLPE JKT TYPE MV-105 (UL) MADE IN USA MMDDYYYY (LIGHTNING BOLT)

Packaging

Non-returnable wood reels in a variety of lengths and dimensions

Performance Compliances

ASTM B3

ASTM B230

ASTM B231

ICEA S-94-649

ICEA T-31-610 (water block compliance), as needed

ICEA T-34-664 (moisture blocked jacket), as needed
AEIC CS8
UL 1072 (MV-105)

RUS U1

Aluminum Unfilled/Filled 35kV 100% I.L. 345 mils

Conductor
Size

AWG/Kcmil

Nom.

Conductor
Diameter

in(mm)

Insulation
Diameter

in(mm)

Concentric

Neutral

No. x AWG

Jacket Thickness
in(mm)

Approx.

Overall
Diameter
in(mm)

Approx. Net

Weight
lbs/kft (kg/km)

 Ampacity
Underground Duct Direct Buried
1/12 Reduced Neutral
1/0 0.362(9.2) 1.12(28.4) 6×14 0.050 (1.3) 1.46(37.1) 795(1,183) 170 195
2/0 0.405(10.3) 1.16(29.5) 6×14 0.050 (1.3) 1.51(38.4) 850(1,265) 195 225
3/0 0.456(11.6) 1.21(30.7) 6×14 0.050 (1.3) 1.56(39.6) 915(1,362) 230 265
4/0 0.512(13.0) 1.27(32.3) 6×14 0.050 (1.3) 1.62(41.1) 995(1,481) 260 295
250 0.558(14.2) 1.32(33.5) 6×14 0.050 (1.3) 1.67(42.2) 1,070(1,592) 290 325
350 0.661(16.8) 1.43(36.3) 6×14 0.075 (1.9) 1.83(46.5) 1,295(1,927) 350 390
500 0.789(20.0) 1.56(39.6) 6×14 0.075 (1.9) 1.96(49.8) 1,525(2,269) 430 480
750 0.968(24.6) 1.75(44.5) 8×14 0.075 (1.9) 2.18(55.4) 1,975(2,939) 525 585
1000 1.117(28.4) 1.91(48.5) 10×14 0.075 (1.9) 2.33(59.2) 2,345(3,489) 615 685
1250 1.250(31.8) 2.05(52.1) 12×14 0.075 (1.9) 2.48(63.0) 2,715(4,040) 715 765
1/6 Reduced Neutral
1/0 0.362(9.2) 1.12 (28.4) 6x14 0.050 (1.3) 1.46 (37.1) 795(1,183) 170 195
2/0 0.405(10.3) 1.16 (29.5) 6x14 0.050 (1.3) 1.51 (38.4) 850(1,265) 195 225
3/0 0.456(11.6) 1.21 (30.7) 6x14 0.050 (1.3) 1.56 (39.6) 915(1,362) 230 265
4/0 0.512 (13.0) 1.27 (32.3) 6x14 0.050 (1.3) 1.62 (41.1) 995(1,481) 260 295
250 0.558 (14.2) 1.32(33.5) 6x14 0.050 (1.3) 1.67 (42.4) 1,070(1,592) 285 325
350 0.661 (16.8) 1.43 (36.3) 7x14 0.075 (1.9) 1.83 (46.5) 1,305(1,942) 350 390
500 0.789 (20.0) 1.56(39.6) 9x14 0.075 (1.9) 1.96 (49.8) 1,560(2,321) 430 480
750 0.968 (24.6) 1.75(44.5) 14x14 0.075 (1.9) 2.18(55.4) 2,045(3,043) 520 580
1000 1.117 (28.4) 1.91 (48.5) 18x14 0.075 (1.9) 2.33(59.2) 2,440(3,631) 610 670
1250 1.250(31.8) 2.05(52.1) 23x14 0.075 (1.9) 2.48(63.0) 2,850(4,241) 700 745
1/3 Reduced Neutral
1/0 0.362(9.2) 1.12 (28.4) 6x14 0.050 (1.3) 1.46 (37.1) 795(1,183) 170 195
2/0 0.405(10.3) 1.16 (29.5) 6x14 0.050 (1.3) 1.51 (38.4) 850(1,265) 195 225
3/0 0.456(11.6) 1.21 (30.7) 7x14 0.050 (1.3) 1.56 (39.6) 930(1,384) 230 265
4/0 0.512 (13.0) 1.27 (32.3) 8x14 0.050 (1.3) 1.62 (41.1) 1,020(1,518) 260 295
250 0.558 (14.2) 1.32(33.5) 10x14 0.050 (1.3) 1.67 (42.4) 1,120(1,667) 285 325
350 0.661 (16.8) 1.43 (36.3) 13x14 0.075 (1.9) 1.83 (46.5) 1,375(2,046) 350 390
500 0.789 (20.0) 1.56(39.6) 18x14 0.075 (1.9) 1.96 (49.8) 1,670(2,485) 425 470
750 0.968 (24.6) 1.75(44.5) 26x14 0.075 (1.9) 2.18(55.4) 2,190(3,259) 515 565
1000 1.117 (28.4) 1.91 (48.5) 23x12 0.075 (1.9) 2.37 (60.2) 2,710(4,032) 595 645
1250 1.250(31.8) 2.05(52.1) 28x12 0.075 (1.9) 2.51 (63.8) 3,155(4,695) 680 710
Full Neutral
1/0 0.362(9.2) 1.12 (28.4) 12x14 0.050 (1.3) 1.46 (37.1) 865(1,287) 170 195
2/0 0.405(10.3) 1.16 (29.5) 14x14 0.050 (1.3) 1.51 (38.4) 945(1,406) 195 225
3/0 0.456(11.6) 1.21 (30.7) 18x14 0.050 (1.3) 1.56 (39.6) 1,060(1,577) 230 260
4/0 0.512 (13.0) 1.27 (32.3) 22x14 0.050 (1.3) 1.62 (41.1) 1,185(1,736) 255 295
250 0.558 (14.2) 1.32(33.5) 26x14 0.050 (1.3) 1.67 (42.4) 1,310(1,949) 280 320
350 0.661 (16.8) 1.43 (36.3) 23x14 0.075 (1.9) 1.86 (47.2) 1,695(2,522) 345 380
500 0.789 (20.0) 1.56(39.6) 21x14 0.075 (1.9) 2.04 (51.8) 2,175(3,236) 415 455
750 0.968 (24.6) 1.75(44.5) 31x14 0.075 (1.9) 2.26 (57.4) 2,910(4,330) 495 540
 
CERTIFICATIONS

 

35kV Type MV-105 cable

PACKAGING

 

tree retardant XLPE concentric neutral XLPE jacket cable
Large Wooden Reel
35kV 100 percent insulation level Primary UD cable
Large Wooden Reel
APPLICATION

 

Primary UD cable 35kV 100% IL MV-105
Industrial Plant
aluminum TR-XLPE CN XLPE 35kV cable
Mining Facility
AL TRXLPE CN XLPE 35kV Primary UD cable
Power Plant
CASE

 

35kV MV-105 utility cable

Battery energy storage system

35kV XLPE jacket Primary UD cable

Bechatw Power Station

MV-105 cable with moisture blocked XLPE jacket

Bingham Canyon Mine

WHY CHOOSE US

 

30Years of experience
in one-stop service

Dongguan Greater Wire & Cable Co., Ltd. is a professional engineering-grade cable manufacturer in China, supplying certified electrical cable solutions for building, industrial, mining, energy, and infrastructure projects worldwide.

With a 30,000 m² factory, 30 production lines, experienced engineers, and a strict quality control team, we provide reliable, traceable, and compliant cable products for international engineering applications. Our products are supported by certifications including SAA, UL, cUL, VDE, TÜV, CE, CB, IEC, BPS, and ISO.

We are committed to safety, quality, transparency, and long-term partnership. From raw material inspection to finished product testing, every batch is carefully controlled to ensure stable performance and dependable project use.

Greater Cable - Certified Quality. Reliable Supply. Engineering Value.

full neutral 35kV MV-105 Primary UD cable
 
15K
Finished Projects
150+
professional staff
15K
happy clients
92+
awards & certifacates
PLANT EQUIPMENT

 

full neutral TR-XLPE CN XLPE MV-105 cable
 
full neutral 35kV aluminum URD cable
 
full neutral single conductor aluminum Primary UD cable
 
one third reduced neutral TR-XLPE CN XLPE MV-105 cable
 
copper concentric neutral 35kV aluminum URD cable
 
helically applied copper neutral wires aluminum underground primary distribution cable
 
GLOBAL CERTIFICATIONS

 

TR-XLPE CN XLPE Power MV-105 Type Primary UD 35kV 100%

CUSTOMER PHOTOS
 

1/0 AWG 35kV 100% IL TR-XLPE cable

INTERNATIONL TRANSPORTATION

 

01

Sea Freight

We offer reliable sea freight solutions for large-volume orders. Your goods are securely packed and shipped in containers, ensuring cost-effective delivery to ports worldwide.

02

Air Freight

For faster delivery, our air freight service ensures your products reach international destinations quickly, with careful handling and full tracking along the way.

03

International Express

Need urgent shipments? Our international express service delivers small to medium orders efficiently, providing door-to-door service with real-time tracking for peace of mind.

1/0 AWG 35kV aluminum URD MV-105 cable
COOPERATIVE PARTNER

 

We are looking for a cooperative partner to expand our business.

1/0 AWG 35kV concentric neutral Primary UD cable
35kV copper concentric neutr1/0 AWG 35kV XLPE jacket MV-105 cableal aluminum cable
1/0 AWG 35kV direct burial Primary UD cable
2/0 AWG 35kV MV-105 Primary UD cable
2/0 AWG 35kV 100% aluminum Primary UD cable
2/0 AWG TR-XLPE CN XLPE MV-105 cable
2/0 AWG 35kV 100% IL TR-XLPE cable
2/0 AWG 35kV XLPE jacket MV-105 cable
2/0 AWG 35kV direct burial Primary UD cable
3/0 AWG TR-XLPE CN XLPE MV-105 cable
How To Cooperate With Us?

Simply share your requirements, receive our professional solution, confirm samples, and enjoy fast, reliable production and worldwide delivery - working with us is that easy.

Our address

Building 2, No. 40 Luxi 2nd Road, Liaobu Town, Dongguan City, Guangdong Province, China

Phone Number

+86 136 6257 9592

+86 135 1078 4550

E-mail

manager01@greaterwire.com

3/0 AWG 35kV XLPE jacket MV-105 cable
FAQ

 

What makes MV-105 rating important for 35kV cables?
MV-105 allows 105°C continuous conductor temperature, providing higher ampacity and better performance in high ambient temperature conditions such as power plants and heavy industrial facilities.
What is the jacket material and why is it significant?
The XLPE jacket offers excellent resistance to moisture, chemicals, and mechanical stress, making it ideal for the demanding environmental conditions of underground installations.
How does the 345 mils insulation thickness compare to other 35kV cables?
345 mils is the standard insulation thickness for 35kV 100% insulation level cables, providing the necessary dielectric strength for the voltage rating.
Is this cable suitable for cable tray installations?
Primary UD cables are specifically designed for underground applications. For cable tray installations, consult the manufacturer to confirm suitability and installation requirements.

 

Hot Tags: 35kV Concentric Neutral Cable Aluminum TR-XLPE Medium Voltage Primary UD MV105 Wire 100% I. L. 345 Mils, China 35kV Concentric Neutral Cable Aluminum TR-XLPE Medium Voltage Primary UD MV105 Wire 100% I. L. 345 Mils manufacturers, suppliers, factory

Send Inquiry