● Conductors: Uncoated soft copper per ASTM B-3. Sizes smaller than #8 are compress-stranded per ASTM B-8. Sizes #8 and larger are compact stranded per ASTM B-496.
● Insulation: Okonite-FMR meets or exceeds requirements of UL 1581, ICEA S-73-532 (NEMA WC57), and ICEA S-95-658 NEMA WC70 Type II insulation.
● Color Coding: Base colors and tracers as shown on the reverse of the Data Sheet, and for sizes #8 AWG and larger, black conductors with surface printing of numbers per ICEA S-73-532 NEMA/WC57 Method 4.
● Grounding Conductor: Where indicated, bare or green insulated stranded copper per ASTM B-8 for sizes #8 AWG and smaller, compact round for sizes larger than #8 AWG per ASTM B-496 and under NEC Table 250.122.
● Assembly: Conductors cabled following UL 1277 using fillers, as necessary, with a cable tape overall.
● Overall Jacket: Complies with UL 1277. The Okolon TS-CPE compound meets or exceeds the requirements of UL 1581.
Application
TC-ER tray cable is permitted for use on power, lighting, control, and signal circuits; indoors or outdoors; in cable trays, raceways, direct burial in the ground, or where supported in outdoor locations by a messenger wire; for Class 1 circuits as permitted in
Article 725 of the NEC; and in cable trays in Class I, Division 2 hazardous locations in industrial establishments where the conditions
of maintenance and supervision ensure that only qualified persons will service the installation.
Cables Marked TC-ER may also be used between a cable tray and the utilization equipment or device when installed in accordance
with NEC 336.10(7).

Feature

TC-ER (Tray Cable - Exposed Installation) cable has passed the vertical tray flame retardant test of IEEE 383-1974 and 1202/FT4, as well as the high-intensity flame retardant standard (210,000 BTU/hr.) of UL 1277 and ICEA T-29-520, showing excellent fire resistance. Its insulated conductor types include XHH/XHHW-2 and cUL-rated RW75/RW90, which can maintain excellent performance at extremely low temperatures of -40°C, and the lowest installation temperature can reach -35°C, providing a convenient solution for applications in cold regions.
Certification
TC-ER Wire (Tray Cable - Exposed Run) cable is UL certified, which means that the product has been rigorously tested and meets the requirements of the North American Electrical Wiring Code (NEC), and ensures safety in exposed environments.
TC-ER cables must undergo durability tests, flexibility tests, mechanical performance tests, and other tests before they can obtain UL certification, providing users with high-security and reliable cable products and reducing the risk of accidents.

Package

Production Line

Greater Wire manufacturer's advanced cable factory has an intelligent and digital manufacturing environment. Through the seamless integration of cutting-edge technology, the factory successfully eliminates errors and defects that may occur in the traditional manual assembly process. The shift to digital manufacturing not only increases efficiency but also demonstrates our commitment to providing our customers with products of the highest reliability. The smart factory framework ensures a streamlined and error-free production process, minimizing the possibility of human-related variances and increasing previously unattainable precision. Accurate and automated inspection mechanism, the factory strictly adheres to quality control. Products are thoroughly inspected from the beginning to the final stage of the manufacturing process. Digital intelligent image detection and laser technologies are used to ensure that each product meets the strict standards set by our company. This commitment to quality extends to our inspection accuracy, with automated production equipment achieving an impressive accuracy of 0.002 mm, exceeding industry benchmarks.
customer

Partner

FAQ
Q: What is the full name of TC-ER cable?
Q: What are the durable features of TC-ER wire?
Q: Are TC-ER wires waterproof?
Hot Tags: ul tc-er wire (xhh/xhhw-2), China ul tc-er wire (xhh/xhhw-2) manufacturers, suppliers, factory, HO5RN F Cable, ul thhn wire, Solar Cable 1500V H1Z2Z2 K TUV UL EN 50618 Solar PV Cable, 300 300V 2 3 4 Core H03VV F Cable, silicone insulated wire, flexible cable

|
Conductor Size
AWG/kcmil
|
Number of Conductors
|
UL TC TYPE
|
Insulation Thickness - mils
|
Jacket Thickness - mils
|
Jacket Thickness - mm
|
Approx. O.D. - Inches
|
Approx O.D. - mm
|
Cross-Sectional
Area (sq. in.)
|
Approx. Net Weight
lbs./1000'
|
Approx. Ship Weight
lbs./1000'
|
90°C Wet or Dry
NEC Ampacity (1)*
|
75°C Wet
NEC Ampacity
|
|
14(7X)
|
2 | TC | 30 | 45 | 1.14 | 0.39 | 9.8 | 0.12 | 95 | 115 | 15 | 15 |
| 3 | TC-ER | 45 | 1.14 | 0.41 | 10.3 | 0.13 | 115 | 135 | 15 | 15 | ||
| 4 | TC-ER | 45 | 1.14 | 0.44 | 11.3 | 0.15 | 140 | 160 | 15 | 15 | ||
| 5 | TC-ER | 45 | 1.14 | 0.48 | 12.2 | 0.18 | 165 | 185 | 15 | 15 | ||
| 7 | TC-ER | 45 | 1.14 | 0.52 | 13.3 | 0.21 | 200 | 220 | 15 | 14 | ||
| 9 | TC-ER | 60 | 1.52 | 0.64 | 16.2 | 0.32 | 290 | 310 | 15 | 14 | ||
| 12 | TC-ER | 60 | 1.52 | 0.71 | 18.1 | 0.40 | 370 | 390 | 12 | 10 | ||
| 19 | TC-ER | 60 | 1.52 | 0.83 | 21.0 | 0.54 | 510 | 530 | 12 | 10 | ||
| 37 | TC-ER | 80 | 2.03 | 1.14 | 29.1 | 0.03 | 985 | 1005 | 10 | 8 | ||
| 12(7X) | 2 | TC | 30 | 45 | 1.14 | 0.42 | 10.7 | 0.14 | 120 | 140 | 20 | 20 |
| 3 | TC-ER | 45 | 1.14 | 0.45 | 11.3 | 0.16 | 145 | 165 | 20 | 20 | ||
| 4 | TC-ER | 45 | 1.14 | 0.49 | 12.4 | 0.19 | 180 | 200 | 20 | 20 | ||
| 5 | TC-ER | 45 | 1.14 | 0.53 | 13.5 | 0.22 | 220 | 240 | 20 | 20 | ||
| 7 | TC-ER | 60 | 1.52 | 0.61 | 15.5 | 0.29 | 295 | 315 | 20 | 17 | ||
| 9 | TC-ER | 60 | 1.52 | 0.70 | 17.9 | 0.39 | 390 | 410 | 20 | 17 | ||
| 12 | TC-ER | 60 | 1.52 | 0.79 | 20.0 | 0.49 | 500 | 520 | 15 | 12 | ||
| 19 | TC-ER | 80 | 2.03 | 0.96 | 24.4 | 0.72 | 745 | 765 | 15 | 12 | ||
| 37 | TC-ER | 80 | 2.03 | 1.27 | 32.3 | 1.27 | 1355 | 1375 | 12 | 10 | ||
|
10(7X)
|
2 | TC | 30 | 45 | 1.14 | 0.47 | 11.9 | 0.17 | 160 | 180 | 30 | 30 |
| 3 | TC-ER | 45 | 1.14 | 0.50 | 12.7 | 0.19 | 200 | 220 | 30 | 30 | ||
| 4 | TC-ER | 60 | 1.52 | 0.58 | 14.6 | 0.26 | 270 | 290 | 30 | 28 | ||
| 5 | TC-ER | 60 | 1.52 | 0.63 | 15.9 | 0.31 | 325 | 345 | 30 | 28 | ||
| 7 | TC-ER | 60 | 1.52 | 0.68 | 17.3 | 0.36 | 405 | 425 | 28 | 24 | ||
| 9 | TC-ER | 60 | 1.52 | 0.79 | 20.1 | 0.49 | 540 | 560 | 28 | 24 | ||
| 12 | TC-ER | 80 | 2.03 | 0.93 | 23.6 | 0.68 | 745 | 765 | 20 | 17 |
| Conductor Size AWG/kcmil | UL TC TYPE | Number of Conductors | Insulation Thickness - mils | Grounding Conductor AWG* | Jacket Thickness - mils | Jacket Thickness - mm | Approx. O.D. - Inches | Approx O.D. - mm |
Cross-Sectional
Area (sq. in.)
|
Approx. Net Weight
lbs./1000'
|
Approx. Ship Weight
lbs./1000'
|
90°C Wet or Dry
NEC Ampacity (1)*
|
75°C Wet
NEC Ampacity (1)
|
|
8(7X)
|
TC-ER
|
3 | 45 | - | 60 | 1.52 | 0.65 | 16.5 | 0.33 | 323 | 346 | 55 | 50 |
| 3 | 10* | 60 | 1.52 | 0.68 | 17.3 | 0.36 | 396 | 419 | 55 | 50 | |||
| 4 | - | 60 | 1.52 | 0.71 | 18.0 | 0.40 | 414 | 443 | 45 | 40 | |||
| 4 | 10* | 60 | 1.52 | 0.71 | 18.0 | 0.40 | 443 | 472 | 45 | 40 | |||
| 6(7X) | TC-ER | 3 | 45 | - | 60 | 1.52 | 0.73 | 18.5 | 0.42 | 448 | 477 | 75 | 65 |
| 3 | 8* | 60 | 1.52 | 0.73 | 18.5 | 0.42 | 536 | 565 | 75 | 65 | |||
| 4 | - | 60 | 1.52 | 0.80 | 20.3 | 0.50 | 565 | 594 | 60 | 52 | |||
| 4 | 8* | 60 | 1.52 | 0.82 | 20.3 | 0.50 | 662 | 697 | 60 | 52 | |||
|
4(7X)
|
TC
|
3 | 45 | - | 60 | 1.52 | 0.82 | 21.8 | 0.53 | 633 | 668 | 95 | 85 |
|
TC-ER
|
3 | 8* | 60 | 1.52 | 0.82 | 21.8 | 0.53 | 732 | 767 | 95 | 85 | ||
|
TC
|
4 | - | 80 | 2.03 | 0.94 | 23.9 | 0.69 | 851 | 904 | 76 | 68 | ||
|
TC-ER
|
4 | 8* | 80 | 2.03 | 0.95 | 24.1 | 0.71 | 936 | 989 | 76 | 68 | ||
|
2(7X)
|
TC | 3 | 45 | - | 80 | 2.03 | 0.98 | 24.9 | 0.75 | 994 | 1063 | 130 | 115 |
| TC-ER | 3 | 6 | 80 | 2.03 | 0.98 | 24.9 | 0.75 | 1145 | 1214 | 130 | 115 | ||
| TC | 4 | - | 80 | 2.03 | 1.08 | 27.4 | 0.92 | 1227 | 1307 | 104 | 92 | ||
| TC-ER | 4 | 6 | 80 | 2.03 | 1.08 | 27.4 | 0.92 | 1276 | 1356 | 104 | 92 | ||
|
1(19X)
|
TC | 3 | 55 | - | 80 | 2.03 | 1.09 | 27.7 | 0.93 | 1226 | 1338 | 150 | 130 |
| TC-ER | 3 | 6 | 80 | 2.03 | 1.09 | 27.7 | 0.93 | 1398 | 1478 | 150 | 130 | ||
| TC | 4 | - | 80 | 2.03 | 1.20 | 30.5 | 1.13 | 1582 | 1694 | 120 | 104 | ||
| TC-ER | 4 | 6 | 80 | 2.03 | 1.21 | 30.7 | 1.15 | 1662 | 1787 | 120 | 104 | ||
|
1/0(19X)
|
TC | 3 | 55 | - | 80 | 2.03 | 1.17 | 29.7 | 1.08 | 1501 | 1615 | 170 | 150 |
| TC-ER | 3 | 6 | 80 | 2.03 | 1.17 | 29.7 | 1.08 | 1680 | 1805 | 170 | 150 | ||
| TC | 4 | - | 80 | 2.03 | 1.29 | 32.8 | 1.31 | 1917 | 2059 | 136 | 120 | ||
| TC-ER | 4 | 6 | 80 | 2.03 | 1.29 | 32.8 | 1.31 | 1986 | 2128 | 136 | 120 | ||
|
2/0(19X)
|
TC | 3 | 55 | - | 80 | 2.03 | 1.26 | 30.0 | 1.25 | 1812 | 1954 | 195 | 175 |
| TC-ER | 3 | 6 | 80 | 2.03 | 1.26 | 30.0 | 1.25 | 2017 | 2159 | 195 | 175 | ||
| TC | 4 | - | 80 | 2.03 | 1.39 | 35.3 | 1.52 | 2356 | 2508 | 156 | 140 | ||
| TC-ER | 4 | 6 | 80 | 2.03 | 1.39 | 35.3 | 1.52 | 2420 | 2607 | 156 | 140 | ||
|
4/0(19X)
|
TC | 3 | 55 | - | 80 | 2.03 | 1.48 | 37.6 | - | 2697 | 2884 | 260 | 230 |
| TC-ER | 3 | 4 | 80 | 2.03 | 1.49 | 37.8 | - | 2903 | 3090 | 260 | 230 | ||
| TC | 4 | - | 80 | 2.03 | 1.63 | 41.4 | - | 3466 | 3717 | 208 | 184 | ||
| TC-ER | 4 | 4 | 80 | 2.03 | 1.63 | 41.4 | - | 3564 | 4815 | 208 | 184 | ||
|
250(37X)
|
TC | 3 | 65 | - | 80 | 2.03 | 1.62 | 41.1 | - | 2952 | 3095 | 290 | 255 |
| TC-ER | 3 | 4 | 80 | 2.03 | 1.62 | 41.1 | - | 3082 | 3259 | 290 | 255 | ||
| TC | 4 | - |
110
|
2.79
|
1.86 | 47.2 | - | 3965 | 4231 | 232 | 185 | ||
| TC-ER | 4 | 4 | 110 | 2.79 | 1.86 | 47.2 | - | 4093 | 4359 | 232 | 185 | ||
|
350(37X)
|
TC | 3 | 65 | - | 110 | 2.79 | 1.89 | 48.0 | - | 4104 | 4370 | 350 | 310 |
| TC-ER | 3 | 3 | 110 | 2.79 | 1.89 | 48.0 | - | 4207 | 4536 | 350 | 310 | ||
| TC | 4 | - | 110 | 2.79 | 2.08 | 52.8 | - | 5334 | 5681 | 280 | 248 | ||
| TC-ER | 4 | 3 | 110 | 2.79 | 2.08 | 52.8 | - | 5494 | 5841 | 280 | 248 | ||
|
500(37X)
|
TC | 3 | 65 | - | 110 | 2.79 | 2.14 | 54.4 | - | 5658 | 6005 | 430 | 380 |
| TC-ER | 3 | 2 | 110 | 2.79 | 2.14 | 54.4 | - | 5861 | 6208 | 430 | 380 | ||
| TC | 4 | - | 110 | 2.79 | 2.37 | 60.2 | - | 7352 | 7911 | 344 | 304 | ||
| TC-ER | 4 | 2 | 110 | 2.79 | 2.37 | 60.2 | - | 7560 | 8119 | 344 | 304 | ||
|
750(61X)
|
TC | 3 | 80 | - | 110 | 2.79 | 2.57 | 65.3 | - | 8331 | 8958 | 535 | 475 |
| TC-ER | 3 | 1 | 110 | 2.79 | 2.57 | 65.3 | - | 8603 | 9930 | 535 | 475 | ||
| TC | 4 | - | 140 |
3.56
|
2.91 | 73.9 | - | 11080 | 11842 | 428 | 380 | ||
| TC-ER | 4 | 1 | 140 |
3.56
|
2.91 | 73.9 | - | 11343 | 12105 | 428 | 380 | ||
|
1000(61X)
|
TC | 3 | 80 | - | 140 | 3.56 | 2.94 | 74.4 | - | 11078 | 11840 | 615 | 345 |
| TC-ER | 3 | 1 | 140 | 3.56 | 2.94 | 74.4 | - | 11463 | 12396 | 615 | 345 | ||
| TC | 4 | - | 140 | 3.56 | 3.26 | 82.8 | - | 14455 | 15388 | 492 | 430 | ||
| TC-ER | 4 | 1 | 140 | 3.56 | 3.26 | 82.8 | - | 14894 | 15827 | 492 | 430 |