How Long Should The Australian Standard Fireproof Cable Last in A Fire?

Leave a message

The Australian standard fire rated wire should last for at least 120 minutes in a fire.


Australian standard fireproof wires, especially cables that comply with AS/NZS3013 standards, are designed to maintain electrical performance and ensure circuit integrity under fire conditions. According to AS/NZS3013 standard, the electrical performance (circuit integrity) of fire resistant cable types under fire conditions should be maintained for at least 120 minutes (two hours). This standard not only requires cables to remain stable at high temperatures, but also requires them to have a certain degree of mechanical protection when subjected to impact and shear. In addition, the fire resistant wire also needs to undergo a spray test, which is a spray test conducted after the combustion test to verify the integrity of the circuit. The spray time is 180 seconds, and the combustion conditions are 1050 ℃ for 120 minutes. These standards ensure the reliability and safety of Australian standard fire rated wires in the event of a fire, providing people with sufficient time for evacuation and response measures


AS3013 Australian Standard Fire Rated Wire Full Impact Test - Standard Name


AS3013 Electrical Installation - Classification of Fire and Mechanical Properties of Wiring System Components


AS3013 Australian Standard Fire Rated Wire Full Impact Test - Scope of Application


This standard specifies the classification of wiring system components. According to the capabilities of the wiring system, it can be divided into:


(a) The specified time for maintaining circuit integrity under fire conditions;


(b) Maintain circuit integrity to prevent mechanical damage of specified severity.


AS3013 Australian Standard Fire Rated Wire Full Impact Test - Test Introduction


Fire resistance test


Fire resistant cables are placed on cable racks and suspended under a concrete floor, facing a fire source and burning for 120 minutes. During this process, the fire resistant cables are powered on and it is necessary to monitor whether the circuit is unobstructed.

Subsequently, the prototype will be installed on the sprinkler system and sprayed for 3 minutes. It is also necessary to monitor whether the circuit is unobstructed.


Impact cutting test


The fire proof wire is set for impact testing in three different temperature environments, and it is necessary to monitor whether the circuit is unobstructed. Use a specialized tool to perform a step-by-step pressure cutting test and record the maximum force required to cut off the circuit.


AS3013 WS52W rated cable will have the following characteristics


WS - Suitable for inclusion in cabling systems
5- Electrical performance (circuit integrity) for 120 minutes (two hours) under fire conditions
2- Provide moderate level of impact damage protection during normal use
W - Electrical performance (circuit integrity) after exposure to water from elevated sprinkler heads

 

 